The following run times are, in most cases, derived from actual measurements with fully charged new batteries operating under typical load connditions. (The load was a switch-mode power supply with a conservative power factor of 0.65.) The balance of the times are estimated from those measurements. The actual run times for a specific application will vary due to the age and charge level of your batteries, ambient temperature, and the specifics of the load on the UPS.

"ONe" Models- standard floor mount
"ONm" Models- medical grade floor mount
"ONe" Models- extended run wall mount
Standard Models- both floor and rack mount
Extended Run Time- floor models
Extended Run Time- 900va rack mount models
Extended Run Time- 1850va rack mount models
Extended Run Time- wall mount models


Home
Page

Software Kits

60 Hz
120v UPS

50/60 Hz
120v UPS

50/60 Hz 230v UPS

50/60 Hz On-Line

Terms Defined

Model
Index

ESTIMATED ONEAC UPS RUN TIMES -

"ONe" STANDARD FLOOR MOUNT MODELS
"ONm" MEDICAL GRADE FLOOR MOUNT MODELS

Approximate run times in minutes.

VA LOADPOWER UNIT
ONe200AONe200DAONe300AONe300DA
ONe200IONe200DIONe300IONe300DI
  ONm300AONm300D
 ONm300DI
ONm300DJ
7528533092
10018372269
15012251139
200816726
250  620
300  515


Home
Page

Top of
Page

Software Kits

60 Hz
120v UPS

50/60 Hz
120v UPS

50/60 Hz 230v UPS

50/60 Hz On-Line

Terms Defined

Model
Index

ESTIMATED ONEAC UPS RUN TIMES -

"ONe" EXTENDED RUN WALL MOUNT MODELS

Both models ONe200XA and ONe300XA come with an internal battery and the option to add up to 6 external batteries. Maximum load for the ONe200XA is 200va. Approximate run times in hours:minutes.

VA LOADINTERNAL BATTERYNUMBER OF EXTERNAL BATTERY PACKS
123456
502:158:50     
751:346:3212:25    
1001:135:109:55    
1500:483:336:4910:19   
2000:342:354:537:379:49  
2500:251:553:325:407:228:44 
3000:181:262:304:105:286:167:29
VA LOADINTERNAL BATTERY123456
NUMBER OF EXTERNAL BATTERY PACKS


Home
Page

Top of
Page

Software Kits

60 Hz
120v UPS

50/60 Hz
120v UPS

50/60 Hz 230v UPS

50/60 Hz On-Line

Terms Defined

Model
Index

ESTIMATED ONEAC UPS RUN TIMES -

STANDARD MODELS

Approximate run times in minutes.

 POWER UNIT
280
pseudo-
sine
400XR
pseudo-
sine
400
sine
600
pseudo-
sine
600
sine
900
sine
1300
sine
2000
sine
120v 60HzXXXXXXXX
120v 60Hz
Rack Mount
    XXXX
120v 50/60Hz  X  X  
230v 50/60Hz  X XXXX
230v 50/60Hz
Rack Mount
    XXXX
VA LOAD
7525113421138090270450
1002185338562107202310
150185521554170130277
20013381538315295228
25011261226244174197
300 20920203360116
350 17817172852102
400 1471415244489
450   1213213980
500   912193472
600   710152860
700     122352
800     112045
900     91740
1200       1229
1300      1025
1850        17
VA LOAD280
pseudo-
sine
400XR
pseudo-
sine
400
sine
600
pseudo-
sine
600
sine
900
sine
1300
sine
2000
sine
POWER UNIT


Home
Page

Top of
Page

Software Kits

60 Hz
120v UPS

50/60 Hz
120v UPS

50/60 Hz 230v UPS

50/60 Hz On-Line

Terms Defined

Model
Index

ESTIMATED ONEAC UPS RUN TIMES -

FLOOR MOUNT EXTENDED RUN TIME MODELS

The models with an "XA" suffix are 120v 60Hz versions. The models with an "XI" suffix are 230v 50/60Hz versions. Approximate run times in hours:minutes.

POWER UNITVA LOADNUMBER OF BATTERY PACKS
ON600XAON900XAON2000XA
ON600XION900XION2000XI12468
X  1005:5411:12   
X  2003:297:0215:32  
XX 4001:403:438:1412:4117:46
XXX6001:042:345:368:2812:00
 XX8000:482:024:236:259:13
  X10000:381:423:385:077:28
  X15000:221:002:162:564:28
  X18500:160:411:392:093:20
  ON2200XA22000:130:281:161:412:40


Home
Page

Top of
Page

Software Kits

60 Hz
120v UPS

50/60 Hz
120v UPS

50/60 Hz 230v UPS

50/60 Hz On-Line

Terms Defined

Model
Index

ESTIMATED ONEAC UPS RUN TIMES -

900va RACK MOUNT EXTENDED RUN TIME MODELS

For model ON910A. Approximate run times in hours:minutes.

VA LOADNUMBER OF BATTERY PACKS
12345678
5010:30       
755:359:00      
1503:456:00      
2003:005:1510:00     
2502:154:308:15     
3001:303:456:30     
3501:203:255:409:30    
3751:153:155:158:50    
4001:103:054:558:10    
4501:002:404:006:558:15   
5001:002:304:006:107:50   
5500:552:154:005:207:25   
6000:502:003:554:307:008:00  
7000:451:403:204:105:406:458:55 
7500:401:303:004:005:006:058:00 
8000:351:202:503:504:506:007:45 
8400:301:102:403:404:405:507:20 
9000:251:002:303:254:305:457:008:20
VA LOAD12345678
NUMBER OF BATTERY PACKS


Home
Page

Top of
Page

Software Kits

60 Hz
120v UPS

50/60 Hz
120v UPS

50/60 Hz 230v UPS

50/60 Hz On-Line

Terms Defined

Model
Index

ESTIMATED ONEAC UPS RUN TIMES -

1850va RACK MOUNT EXTENDED RUN TIME MODELS

For models ON2010A and ON2110A. Approximate run times in hours:minutes.
NOTE: only model ON2110A can support the 2000va load level.

VA LOADNUMBER OF BATTERY PACKS
12345678
2005:15       
3003:459:30      
4003:058:10      
5002:306:109:25     
6002:004:308:00     
7001:404:106:459:15    
8001:303:506:008:45    
9001:203:135:428:01    
10501:162:555:047:22    
12001:022:374:256:047:24   
13500:502:223:504:456:308:00  
14750:482:143:344:306:027:20  
16000:452:063:184:175:366:488:02 
17250:421:523:013:525:126:157:12 
18500:401:402:453:294:525:426:308:05
20000:301:152:052:353:304:154:506:00
VA LOAD12345678
NUMBER OF BATTERY PACKS


Home
Page

Top of
Page

Software Kits

60 Hz
120v UPS

50/60 Hz
120v UPS

50/60 Hz 230v UPS

50/60 Hz On-Line

Terms Defined

Model
Index

ESTIMATED ONEAC UPS RUN TIMES -

WALL MOUNT EXTENDED RUN TIME MODELS

The models with an "XA" suffix are 120v 60Hz versions. The models with an "XI" suffix are 230v 50/60Hz versions. Approximate run times in hours:minutes.

POWER UNITVA LOADNUMBER OF BATTERY PACKS
ON400XA-WLON600XA-WL
ON400XI-WLON600XI-WL12468
X 1003:156:4414:08  
XX2001:533:568:25  
XX4000:552:004:296:339:05
 X6000:291:112:473:505:28


Home
Page

Top of
Page

Software Kits

60 Hz
120v UPS

50/60 Hz
120v UPS

50/60 Hz 230v UPS

50/60 Hz On-Line

Terms Defined

Model