The 50/60 Hertz versions range from 300va/200w through 2000va/1400w.
UPS Standard Floor Models
UPS Standard Floor Mount "ONe" Models
UPS Medical Grade Floor Mount "ONm" Models
UPS Rack Mount Models
UPS Extended Run Time Floor Models
UPS Extended Run Time Wall Mount Models
Home Page |
Software Kits |
60 Hz 120v UPS |
50/60 Hz 120v UPS |
50/60 Hz On-Line |
Estimated Run Times |
Terms Defined |
Model Index |
MODELS: | UPS Standard Floor Mount |
TYPE: | Multi Phase, 50/60 Hertz |
VOLTAGE: | 230 |
RATINGS: | 400VA-2kVA |
1.7-8.7A | |
250-1400W |
These models come in a variety of plug and receptacle configurations other than those listed. Contact your Gryphon representative for help with your specific application.
MODEL | ON400I | ON600I | 0N900I | 0N1300I | 0N2000I |
---|---|---|---|---|---|
Output Rating (VA) | 400 | 600 | 900 | 1300 | 2000 |
Output Rating (W) | 250 | 400 | 600 | 900 | 1400 |
Frequency (Hz) | 50/60 | 50/60 | 50/60 | 50/60 | 50/60 |
Input/Output Voltage (VAC) | 230 | 230 | 230 | 230 | 230 |
Output Wave Form | Sine | Sine | Sine | Sine | Sine |
Load Regulation (RMS) | ±3% | ±3% | ±3% | ±3% | ±3% |
Inrush - ½ cycle (Amps) | 60 | 80 | 100 | 200 | 240 |
MODEL | ON400I | ON600I | 0N900I | 0N1300I | 0N2000I |
Surge Current (Amps) 1 sec. typical | 12 | 15 | 20 | 40 | 48 |
Surge Current (Amps) 4 sec. typical | 6 | 7.5 | 10 | 20 | 24 |
1kHz Forward Transfer Impedance (Ohms) | <20 | <15 | <12 | <10 | <8 |
Recharge to 60% Capacity (hrs) | 4 | 4 | 4 | 4 | 4 |
Efficiency (%) | >90 | >83 | >83 | >87 | >83 |
MODEL | ON400I | ON600I | 0N900I | 0N1300I | 0N2000I |
Agency Approvals | CE & GS & are tested under EN50081-1, EN50082-1, EN50091, EN55011(CISPR22), EN60950, IEC801-2, IEC801-3, IEC801-4 | ||||
Line Cord (cm) | 180 | 180 | 180 | 180 | 180 |
Input Connector (IEC) | 320 | 320 | 320 | 320 | 320/C20 |
Width (cm) | 21 | 21 | 21 | 21 | 21 |
Height (cm) | 19 | 19 | 31 | 31 | 31 |
Depth (cm) | 39 | 47 | 47 | 53 | 47 |
Shipping Weight (kg) | 17 | 22 | 30 | 43 | 30 |
BATTERY CABINET | |||||
Width (cm) | - | - | - | - | 21 |
Height (cm) | - | - | - | - | 19 |
Depth (cm) | - | - | - | - | 47 |
Shipping Weight (kg) | - | - | - | - | 35 |
MODEL | ON400I | ON600I | 0N900I | 0N1300I | 0N2000I |
Home Page |
Top of Page |
Software Kits |
60 Hz 120v UPS |
50/60 Hz 120v UPS |
50/60 Hz On-Line |
Estimated Run Times |
Terms Defined |
Model Index |
MODELS: | UPS Standard Floor Mount "ONe" Type |
TYPE: | Multi Phase, 50/60 Hertz |
VOLTAGE: | 230 |
RATINGS: | 200VA-300VA |
1.7-2.5A | |
135-200W |
These models each come in 2 versions:
The -SV version has no communication capabilities;
The -SB version has basic communication capabilities built in.
Contact your Gryphon representative for help with your specific application.
MODEL | ONe200I | 0Ne200DI | 0Ne300I | 0Ne300DI |
---|---|---|---|---|
Output Rating (VA) | 200 | 200 | 300 | 300 |
Output Rating (W) | 135 | 135 | 200 | 200 |
Frequency (Hz) | 50 | 50 | 50/60 | 50/60 |
Input/Output Voltage (VAC) | 230 | 230 | 230 | 230 |
Output Wave Form | Pseudo-Sine | Pseudo-Sine | Pseudo-Sine | Pseudo-Sine |
Full Load Backup Time (min) | 5 | 15 | 5 | 15 |
Load Regulation (RMS) | ±3% | ±3% | ±3% | ±3% |
MODEL | ONe200I | ONe200DI | 0Ne300A | 0Ne300DA |
Recharge to 60% Capacity (hrs) | 6-10 | 6-10 | 6-10 | 6-10 |
Agency Approvals | EN50091, EN60950, EN50081-1, EN55022 (CISPR 22), EN50082-1, IEC801-2, IEC801-3, IEC801-4 | |||
Input Connector | IEC320 | IEC320 | IEC320 | IEC320 |
Input Cord | IEC320 M/F detachable | |||
Load Connector | 4@IEC320 | 4@IEC320 | 4@IEC320 | 4@IEC320 |
Width (Inches) | 6 | 6 | 6 | 6 |
Height (Inches) | 7.4 | 7.4 | 7.4 | 7.4 |
Depth (Inches) | 15 | 15 | 15 | 15 |
Shipping Weight (Lbs.) | 32 | 38 | 34 | 40 |
MODEL | ONe200I | ONe200DI | 0Ne300I | 0Ne300DI |
Home Page |
Top of Page |
Software Kits |
60 Hz 120v UPS |
50/60 Hz 120v UPS |
50/60 Hz On-Line |
Estimated Run Times |
Terms Defined |
Model Index |
MODELS: | UPS Medical Grade Floor Mount "ONm" Type |
TYPE: | Multi Phase, 50/60 Hertz |
VOLTAGE: | 230 |
RATINGS: | 300VA |
2.5A | |
200W |
This model comes in a -SI version which has basic communication capabilities built in.
Contact your Gryphon representative for help with your specific application.
MODEL | 0Nm300DI |
---|---|
Output Rating (VA) | 300 |
Output Rating (W) | 200 |
Frequency (Hz) | 50/60 |
Input/Output Voltage (VAC) | 230 |
Output Wave Form | Pseudo-Sine |
Full Load Backup Time (min) | 15 |
Load Regulation (RMS) | ±3% |
Recharge to 60% Capacity (hrs) | 6-10 |
Leakage Current (µamps) | <300 |
MODEL | 0Nm300DI |
Agency Approvals | EN50091, EN60601-1, EN60950, EN50081-1, EN55022 (CISPR 22), EN50082-1, IEC801-2, IEC801-4 |
Input Connector | IEC320 |
Input Cord | Use the cord from the protected piece of equipment. |
Load Connector | 4@IEC320 |
Load Cord | 6' with IEC320 connectors at each end |
Width (Inches) | 6 |
Height (Inches) | 7.4 |
Depth (Inches) | 15 |
Shipping Weight (Lbs.) | 40 |
MODEL | 0Nm300DI |
Home Page |
Top of Page |
Software Kits |
60 Hz 120v UPS |
50/60 Hz 120v UPS |
50/60 Hz On-Line |
Estimated Run Times |
Terms Defined |
Model Index |
MODELS: | UPS Rack Mount |
TYPE: | Multi Phase, 50/60 Hertz |
VOLTAGE: | 230 |
RATINGS: | 600VA-2kVA |
2.6-8.7A | |
600-1400W |
These models come in a variety of plug and receptacle configurations other than those listed. Contact your Gryphon representative for help with your specific application.
MODEL | ON600I-RM | 0N900I-RM | 0N1300I-RM | 0N2000I-RM |
---|---|---|---|---|
Output Rating (VA) | 600 | 900 | 1300 | 2000 |
Output Rating (W) | 400 | 600 | 900 | 1400 |
Frequency (Hz) | 50/60 | 50/60 | 50/60 | 50/60 |
Input/Output Voltage (VAC) | 230 | 230 | 230 | 230 |
Output Wave Form | Sine | Sine | Sine | Sine |
Load Regulation (RMS) | ±3% | ±3% | ±3% | ±3% |
Inrush - ½ cycle (Amps) | 80 | 100 | 200 | 240 |
MODEL | ON600I-RM | 0N900I-RM | 0N1300I-RM | 0N2000I-RM |
Surge Current (Amps) 1 sec. Typical | 15 | 20 | 40 | 48 |
Surge Current (Amps) 4 sec. Typical | 7.5 | 10 | 20 | 24 |
1kHz Forward Transfer Impedance (Ohms) | <15 | <12 | <10 | <8 |
Recharge to 60% Capacity (hrs) | 4 | 4 | 4 | 4 |
Efficiency (%) | >83 | >83 | >87 | >83 |
MODEL | ON600I-RM | 0N900I-RM | 0N1300I-RM | 0N2000I-RM |
Agency Approvals | CE & GS & are tested under EN50081-1, EN50082-1, EN50091, EN55011(CISPR22), EN60950, IEC801-2, IEC801-3, IEC801-4 | |||
Line Cord (cm) | 180 | 180 | 180 | 180 |
Input Connector (IEC) | 320 | 320 | 320 | 320/C20 |
Width (cm) | 48 | 48 | 48 | 48 |
Height (cm) | 18 | 18 | 27 | 27 |
Depth (cm) | 38 | 38 | 38 | 38 |
Shipping Weight (kg) | 23 | 31 | 46 | 33 |
BATTERY CABINET | ||||
Width (cm) | - | - | - | 48 |
Height (cm) | - | - | - | 27 |
Depth (cm) | - | - | - | 23 |
Shipping Weight (kg) | - | - | - | 37 |
MODEL | ON600I-RM | 0N900I-RM | 0N1300I-RM | 0N2000I-RM |
Home Page |
Top of Page |
Software Kits |
60 Hz 120v UPS |
50/60 Hz 120v UPS |
50/60 Hz On-Line |
Estimated Run Times |
Terms Defined |
Model Index |
MODELS: | UPS Extended Run Floor Mount |
TYPE: | Multi Phase, 50/60 Hertz |
VOLTAGE: | 230 |
RATINGS: | 600VA-2kVA |
2.6-8.7A | |
400-1400W |
These models come in a variety of plug and receptacle configurations other than those listed. Contact your Gryphon representative for help with your specific application.
MODEL | ON600XI | 0N900XI | 0N2000XI |
---|---|---|---|
Output Rating (VA) | 600 | 900 | 2000 |
Output Rating (W) | 400 | 600 | 1400 |
Frequency (Hz) | 50/60 | 50/60 | 50/60 |
Input/Output Voltage (VAC) | 230 | 230 | 230 |
Output Wave Form | Sine | Sine | Sine |
Load Regulation (RMS) | ±3% | ±3% | ±3% |
Inrush - ½ cycle (Amps) | 80 | 100 | 240 |
Surge Current (Amps) 1 sec. typical | 15 | 20 | 48 |
Surge Current (Amps) 4 sec. typical | 7.5 | 10 | 24 |
1kHz Forward Transfer Impedance (Ohms) | <15 | <12 | <8 |
MODEL | ON600XI | 0N900XI | 0N2000XI |
Recharge to 60% Capacity (hrs) | 4 | 4 | 4 |
Efficiency (%) | >83 | >83 | >83 |
Agency Approvals | CE & GS & are tested under EN50081-1, EN50082-1, EN50091, EN55011(CISPR22), EN60950, IEC801-2, IEC801-3, IEC801-4 | ||
Line Cord (cm) | 180 | 180 | 180 |
Input Connector (IEC) | 320 | 320 | 320/C20 |
Width (cm) | 21 | 21 | 21 |
Height (cm) | 19 | 30 | 30 |
Depth (cm) | 47 | 47 | 53 |
Shipping Weight (kg) | 22 | 31 | 30 |
BATTERY CABINET | |||
Width (cm) | 21 | 21 | 21 |
Height (cm) | 27 | 27 | 27 |
Depth (cm) | 23 | 23 | 23 |
Shipping Weight (kg) | 34 | 34 | 34 |
MODEL | ON600XI | 0N900XI | 0N2000XI |
Home Page |
Top of Page |
Software Kits |
60 Hz 120v UPS |
50/60 Hz 120v UPS |
50/60 Hz On-Line |
Estimated Run Times |
Terms Defined |
Model Index |
MODELS: | UPS Extended Run Wall Mount |
TYPE: | Multi Phase, 50/60 Hertz |
VOLTAGE: | 230 |
RATINGS: | 400 & 600VA |
1.7 & 2.6A | |
250 & 400W |
These models come in a variety of plug and receptacle configurations other than those listed. Contact your Gryphon representative for help with your specific application.
MODEL | ON400XI-WL | ON600XI-WL |
---|---|---|
Output Rating (VA) | 400 | 600 |
Output Rating (W) | 250 | 400 |
Frequency (Hz) | 50/60 | 50/60 |
Input/Output Voltage (VAC) | 230 | 230 |
Output Wave Form | Sine | Sine |
Load Regulation (RMS) | ±3% | ±3% |
Inrush - ½ cycle (Amps) | 60 | 80 |
Surge Current (Amps) 1 sec. Typical | 12 | 15 |
Surge Current (Amps) 4 sec. Typical | 6 | 7.5 |
1kHz Forward Transfer Impedance (Ohms) | <20 | <15 |
Output Rating (VA) | 400 | 600 |
MODEL | ON400XI-WL | ON600XI-WL |
Recharge to 60% Capacity (hrs) | 4 | 4 |
Efficiency (%) | >90 | >83 |
Agency Approvals | CE & GS & are tested under EN50081-1, EN50082-1, EN50091, EN55011(CISPR22), EN60950, IEC801-2, IEC801-3, IEC801-4 | |
Line Cord (cm) | 180 | 180 |
Input Connector (IEC) | 320 | 320 |
Width (cm) | 21 | 21 |
Height (cm) | 38 | 38 |
Depth (cm) | 23 | 23 |
Shipping Weight (kg) | 13 | 15 |
BATTERY CABINET | ||
Width (cm) | 22 | 22 |
Height (cm) | 27 | 27 |
Depth (cm) | 23 | 23 |
Shipping Weight (kg) | 18 | 18 |
MODEL | ON400XI-WL | ON600XI-WL |