Oneac was founded on the basis of their understanding telephone line problems caused by poor, dirty power. Conventional telephone line protectors (either gas tube or solid state) are designed to clamp above the operating DC bias and the ring voltage level. The Oneac Online's ability to differentiate signals based on frequency permits the useful signals to pass while preventing transients from damaging semiconductor based electronics.
All Oneac telephone line protectors have the following features:
Oneac telephone line protectors fall into 4 product families.
5-Pin base protectors
66 Block M1-50 protectors
Digital Station Protectors
Modular Jack protectors
Online 10 Series (formerly Krone LSA-Plus 237A) protectors
Home Page |
Terms Defined |
Model Index |
MODEL | 5S-AP | 5S-DP |
---|---|---|
Type | Analog | Digital |
Typical Usage | Standard Service Trunk Lines, Analog OPX Stations w/ Ring Signal | ISDN, Digital OPX Stations w/o Ring Signal |
Transient Voltage Performance w/ 1/1µs, 200v Peak (volts) | 28 | 28 |
Impulse Voltage Performance w/ 10/1000µs, 1500v, 100a (volts) | 100 | 50 |
DC Breakdown Voltage @ 2000v/sec (volts) | 280 | 70 |
Rated Impulse Discharge w/ 10/1000µs (amps) | 100 | 100 |
Response Time (nanoseconds) | <1 | <1 |
DC Holdover @25°C, 20ms Max (ma) | 200 | 200 |
On State Voltage w/ 1amp RMS (volts) | <5 | <5 |
MODEL | 5S-AP | 5S-DP |
Capacitance @ 50vdc, 5vac, 1khz (pf) | <200 | <200 |
Insulation Resistance (Megohms) | >100 | >100 |
Service Life w/ 10/1000µs @±10a | Unlimited | Unlimited |
Service Life w/ 10/1000µs @±100a | Unlimited | Unlimited |
Service Life w/ 10/1000µs @±300a | Fail-Safe | Fail-Safe |
Resettable Overcurrent Protection (Sneak Current) @25°C (ma) | 300 | 300 |
UL Listing # | 497 | 497 |
Storage Temperature (°C) | -40 to +85 | -40 to +85 |
Operating Temperature (°C) | -40 to +65 | -40 to +65 |
Test Points | Yes | Yes |
Color Code | Black | Yellow |
MODEL | 5S-AP | 5S-DP |
Home Page |
Top of Page |
Terms Defined |
Model Index |
MODEL: 66 Block M1-50 Protectors
A ground bar (p/n 350-032) is required to tie these units to ground.
MODEL | 6-AP | 6-DC | 6-DP | 6-DA |
---|---|---|---|---|
Type | Analog | Digital | Digital | Data |
Typical Usage | Standard Service Trunk Lines, Analog OPX Stations w/ Ring Signal | T-1 (DS-1) Digital Carrier, Digital Data | ISDN, Digital OPX Stations w/o Ring Signal | Token Ring, Ethernet |
Transient Voltage Performance w/ 1/1µs, 200v Peak (volts) | 28 | 28 | 28 | 28 |
Impulse Voltage Performance w/ 10/1000µs, 1500v, 100a (volts) | 100 | 100 | 50 | 50 |
DC Breakdown Voltage @ 2000v/sec (volts) | 280 | 280 | 70 | 30 |
MODEL | 6-AP | 6-DC | 6-DP | 6-DA |
Rated Impulse Discharge w/ 10/1000µs (amps) | 100 | 100 | 100 | 100 |
Response Time (nanoseconds) | <1 | <1 | <1 | <1 |
DC Holdover @25°C, 20ms Max (ma) | 200 | 200 | 200 | 200 |
On State Voltage w/ 1amp RMS (volts) | <5 | <5 | <5 | <5 |
Capacitance @ 50vdc, 5vac, 1khz (pf) | <200 | <200 | <200 | <200 |
Insulation Resistance (Megohms) | >100 | >100 | >100 | >100 |
Fused (Fails Open) | Yes | Yes | Yes | Yes |
Service Life w/ 10/1000µs @±10a | Unlimited | Unlimited | Unlimited | Unlimited |
MODEL | 6-AP | 6-DC | 6-DP | 6-DA |
Service Life w/ 10/1000µs @±100a | Unlimited | Unlimited | Unlimited | Unlimited |
Service Life w/ 10/1000µs @±300a | Fail-Safe | Fail-Safe | Fail-Safe | Fail-Safe |
Resettable Overcurrent Protection (Sneak Current) @25°C (ma) | 300 | 300 | 300 | 250 |
UL Listing # | 497, 497A | 497, 497A | 497, 497A | 497, 497A |
Storage Temperature (°C) | -40 to +85 | -40 to +85 | -40 to +85 | -40 to +85 |
Operating Temperature (°C) | -40 to +65 | -40 to +65 | -40 to +65 | -40 to +65 |
Test Points | Yes | Yes | Yes | Yes |
Color Code | Black | Blue | Yellow | White |
MODEL | 6-AP | 6-DC | 6-DP | 6-DA |
Home Page |
Top of Page |
Terms Defined |
Model Index |
MODEL: Digital Station Protectors
A ground bar (p/n 350-032) is required to tie these units to ground.
MODEL | 6-DSP10 | 6-DSP20 | 6-DSP36 | 6-DSP68 |
---|---|---|---|---|
Type | Analog | Digital | Digital | Data |
Typical Usage | 10BaseT Applic. w/ No Feed & 5V Logic Signals | Executone Applic. w/12V Feed & 5V Logic Signals | Nortel & ROLM/Siemens Applic. w/28V Feed & 12V Logic Signals | Fujitsu Applic. w/48V Feed & 5V Logic Signals |
Transient Voltage Performance w/ 1/1µs, 200v Peak (volts) | 28 | 28 | 28 | 28 |
Impulse Voltage Performance w/ 10/1000µs, 1500v, 100a (volts) | 100 | 100 | 50 | 50 |
DC Breakdown Voltage @ 2000v/sec (volts) | 280 | 280 | 70 | 30 |
MODEL | 6-DSP10 | 6-DSP20 | 6-DSP36 | 6-DSP68 |
Rated Impulse Discharge w/ 10/1000µs (amps) | 100 | 100 | 100 | 100 |
Response Time (nanoseconds) | <1 | <1 | <1 | <1 |
DC Holdover @25°C, 20ms Max (ma) | 200 | 200 | 200 | 200 |
On State Voltage w/ 1amp RMS (volts) | <5 | <5 | <5 | <5 |
Capacitance @ 50vdc, 5vac, 1khz (pf) | <200 | <200 | <200 | <200 |
Insulation Resistance (Megohms) | >100 | >100 | >100 | >100 |
Fused (Fails Open) | Yes | Yes | Yes | Yes |
Service Life w/ 10/1000µs @±10a | Unlimited | Unlimited | Unlimited | Unlimited |
MODEL | 6-DSP10 | 6-DSP20 | 6-DSP36 | 6-DSP68 |
Service Life w/ 10/1000µs @±100a | Unlimited | Unlimited | Unlimited | Unlimited |
Service Life w/ 10/1000µs @±300a | Fail-Safe | Fail-Safe | Fail-Safe | Fail-Safe |
Resettable Overcurrent Protection (Sneak Current) @25°C (ma) | 300 | 300 | 300 | 250 |
UL Listing # | 497, 497A | 497, 497A | 497, 497A | 497, 497A |
Storage Temperature (°C) | -40 to +85 | -40 to +85 | -40 to +85 | -40 to +85 |
Operating Temperature (°C) | -40 to +65 | -40 to +65 | -40 to +65 | -40 to +65 |
Test Points | Yes | Yes | Yes | Yes |
Color Code | Black | Blue | Yellow | White |
MODEL | 6-DSP10 | 6-DSP20 | 6-DSP36 | 6-DSP68 |
Home Page |
Top of Page |
Terms Defined |
Model Index |
MODEL: Modular Jack Protectors
A ground wire is provided with these units to tie them to ground.
Jack Openings Pair Locations | Connector Type | Suffix | Pairs Protected |
6 position, 2 wire, 1 pair | 11 | (3,4) | |
6 position, 4 wire, 2 pair | 14 | (3,4);(2,5) | |
8 position, 8 wire, 4 pair | 45 | (1,8);(2,7);(3,6);(4,5) |
Each of the RJ models in the chart below ends with an "xx". The "xx" must be replaced by a two digit number from the suffix chart above. (For example: the full model number for an analog protector for a 6 position 2 wire connector would be RJ-AP11.)
MODEL | RJ-APxx | LJ-APxx | RJ-DPxx | RJ-DAxx |
---|---|---|---|---|
Allowed Suffixes | 11,14,45 | 11,14,45 | 11,14,45 | 45 |
Type | Analog | Analog | Digital | Data |
Location | US | International | US | US |
Typical Usage | Standard Service Trunk Lines, Analog OPX Stations w/ Ring Signal | Standard Service Analog-Fax, Modem & Data Terminal | ISDN, Digital OPX Stations w/o Ring Signal | Low Volage Data Circuits |
Transient Voltage Performance w/ 1/1µs, 200v Peak (volts) | 28 | 30 typical, 40 max | 28 | 28 |
Impulse Voltage Performance w/ 10/1000µs, 1500v, 100a (volts) | 100 | 530 typical, 600 max w/ 1 input tied to earth: 100 typical, 170 max | 50 | 50 |
MODEL | RJ-APxx | LJ-APxx | RJ-DPxx | RJ-DAxx |
DC Breakdown Voltage @ 2000v/sec (volts) | 280 | 420 min, 600 max | 70 | 30 |
Rated Impulse Discharge w/ 10/1000µs (amps) | 100 | 100 | 100 | 100 |
Response Time (nanoseconds) | <1 | <1 | <1 | <1 |
DC Holdover @25°C, 20ms Max, ±5vdc (ma) | 200 | 200 | 200 | 200 |
On State Voltage w/ 1amp RMS (volts) | <5 | <100 | <5 | <5 |
Capacitance @ 50vdc, 5vac, 1khz (pf) | <200 | <200 | <200 | - |
MODEL | RJ-APxx | LJ-APxx | RJ-DPxx | RJ-DAxx |
Capacitance @ 5vdc, 1vac, 10khz-10mhz (pf) | - | - | - | <200 |
Insulation Resistance (Megohms) | >100 | >100 | >100 | >100 |
Input Fused | Yes | Yes | Yes | Yes |
Max Loop Resistance @25°C (Ohms) | 40 | 40 | 40 | - |
Service Life w/ 10/1000µs @±10a | Unlimited | Unlimited | Unlimited | Unlimited |
Service Life w/ 10/1000µs @±100a | Unlimited | Unlimited | Unlimited | Unlimited |
MODEL | RJ-APxx | LJ-APxx | RJ-DPxx | RJ-DAxx |
Service Life w/ 10/1000µs @±300a | Fail-Safe | Fail-Safe | Fail-Safe | Fail-Safe |
Resettable Overcurrent Protection (Sneak Current) @25°C (ma) | 300 | 300 | 300 | - |
UL Listing # | 497, 497A | 497, 497A | 497, 497A | 497, 497A |
Storage Temperature (°C) | -40 to +85 | -40 to +85 | -40 to +85 | -40 to +85 |
Operating Temperature (°C) | -40 to +65 | -40 to +65 | -40 to +65 | -40 to +65 |
MODEL | RJ-APxx | LJ-APxx | RJ-DPxx | RJ-DAxx |
Home Page |
Top of Page |
Terms Defined |
Model Index |
MODEL: OnLine 10 Series (formerly Krone LSA-Plus 237A) Protectors
A ground bar (p/n 350-139) is required to tie the single position units to ground.
MODEL | 10AP-1U | 10DP-1U | 10-APU | 10-DPU |
---|---|---|---|---|
Type | Analog | Digital | Analog | Digital |
Location | US | US | UK | UK |
Typical Usage | Standard Service Trunk Lines, Analog OPX Stations w/ Ring Signal | ISDN, Digital OPX Stations w/o Ring Signal | Standard Service Trunk Lines, Analog OPX Stations w/ Ring Signal | ISDN, Digital OPX Stations w/o Ring Signal |
Positions | 1 | 1 | 10 | 10 |
Transient Voltage Performance w/ 1/1µs, 200v Peak (volts) | 28 | 28 | 28 | 28 |
Impulse Voltage Performance w/ 10/1000µs, 1500v, 100a (volts) | 100 | 50 | 100 | 50 |
MODEL | 10AP-1U | 10DP-1U | 10-APU | 10-DPU |
DC Breakdown Voltage @ 2000v/sec (volts) | 280 | 70 | 280 | 70 |
Rated Impulse Discharge w/ 10/1000µs (amps) | 100 | 100 | 100 | 100 |
Response Time (nanoseconds) | <1 | <1 | <1 | <1 |
DC Holdover @25°C, 20ms Max, ±5vdc (ma) | 200 | 200 | 200 | 200 |
On State Voltage w/ 1amp RMS (volts) | <5 | <5 | <5 | <5 |
Capacitance @ 50vdc, 5vac, 1khz (pf) | <200 | <200 | <200 | <200 |
MODEL | 10AP-1U | 10DP-1U | 10-APU | 10-DPU |
Insulation Resistance (Megohms) | >100 | >100 | >100 | >100 |
Fused (Fails Open) | Yes | Yes | Yes | Yes |
Service Life w/ 10/1000µs @±10a | Unlimited | Unlimited | Unlimited | Unlimited |
Service Life w/ 10/1000µs @±100a | Unlimited | Unlimited | Unlimited | Unlimited |
Service Life w/ 10/1000µs @±300a | Fail-Safe | Fail-Safe | Fail-Safe | Fail-Safe |
MODEL | 10AP-1U | 10DP-1U | 10-APU | 10-DPU |
Resettable Overcurrent Protection (Sneak Current) @25°C (ma) | 300 | 300 | 300 | 300 |
UL Listing # | 497A | 497A | 497A | 497A |
Storage Temperature (°C) | -40 to +85 | -40 to +85 | -40 to +85 | -40 to +85 |
Operating Temperature (°C) | -40 to +65 | -40 to +65 | -40 to +65 | -40 to +65 |
Test Points | Yes | Yes | No | No |
Color Code | Black | Yellow | White | Yellow |
MODEL | 10AP-1U | 10DP-1U | 10-APU | 10-DPU |
Home Page |
Top of Page |
Terms Defined |
Model Index |