Gryphon, Inc.

Home Icon Email Icon

POWER LINE MONITORING EQUIPMENT

Gryphon carries power line monitoring equipment and services designed specifically for non-technical personnel. Our products and services give all the detail you need with a minimum of excess data or complex setups.

Oneac Onegraph® Power Line Monitor
Oneac Line Viewer
RX Monitoring Services


Home
Page

Terms Defined

Model
Index

MODEL: Onegraph® Power Line MonitorPDF Icon Download Spec Sheets

The Onegraph® Power Line monitor is designed to provide a picture of the electrical environment experienced by your equipment over time.

Power Requirement90-140 or 180-270v @ 50/60Hz, 950ma
Output TypePaper strip chart on demand
AC Line Voltage Measurement Channel11 user-selectable line-to-neutral voltages from 100 to 250v
Voltage Channel Output DataDate, time & duration of each surge or sag
Common & Normal Mode Noise Measurement Channel1-1000v or 1-6000v user selectable
Noise Channel Output DataBar chart for each time segment showing size of noise pulse
AC Input ConnectorsIEC320
Backup Battery Rating3 amp-hours nominal
Report Time Scale8 hrs or 6 days, user selectable
Calibration AdjustmentsNone
Carrying CaseSoft sided Cordura
Dimensions6.5"H, 12"W, 11"L
Shipping Weight10 Lbs.


Home
Page

Top of
Page

Terms Defined

Model
Index

MODEL: Line Viewer

The power line noise viewer interfaces between the power line and a 2 channel oscilloscope. The viewer isolates common mode and normal mode noise pulses for immediate viewing as they occur.

Model NumberWV102
Maximum Input Voltage (RMS)250
Output Voltage Channel Sensitivity100:1
Output Voltage Channel Bandwidth10 to 50Hz
Noise Voltage Channel Sensitivity10:1
Noise Voltage Channel Bandwidth6kHz to 5MHz
Dynamic Rangeper IEEE 587-1980, Part A Ring Wave up to 6000v
Input ConnectorIEC320
Output ConnectorsBNC
Isolation (power line to BNC connector)2000v
Dimensions2.25"H, 3.2"W, 5.9"L
Shipping Weight2 Lbs.


Home
Page

Top of
Page

Terms Defined

Model
Index

MODEL: RX Monitoring Services

RX Monitoring Services (RxMS) can remotely test a site's power and environmental conditions either prior to installation of equipment or whenever a problem is suspected. In the past if a site's power needed to be checked, a specially trained technician would have to visit the site. Such a visit is expensive and time consuming. RxMS tests are expressly designed to be set up by untrained personnel alone.

RxMS offers the Automated Site Assistance Program (ASAP) for those who need an automated method for their initial site inspection and documentation process. RxMS offers an advanced electronic monitoring system that can measure the electrical power and ground quality, temperature, humidity, vibration, air purity, DC voltage, and more in accordance with the environmental requirements of the specific equipment to be installed. Using Remote Processing Technology (RPT) developed by RxMS engineers, data is gathered at your site, downloaded to a central computer at RxMS, evaluated for specific site conditions and, typically within 24 hours, compiled into a report. The report includes a comprehensive analysis of the data recorded, an easy to read executive summary, and a recommendation of any action that may be needed. This service fits in ideally with ISO 9000 quality procedures in that it fully documents the conditions of the site at the initial installation and clearly notifies you of any deviations from that required by the equipment to be installed. Fast, accurate, economical, easy to use makes this service ideal.

RxMS maintains an extensive list of electronic equipment and their environmental requirements. Contact us to determine how your equipment can be included in our listing.

RxMS can be obtained as a one time test or as a longer term commitment for those organizations needing many tests at different sites over time. Normal service includes (special needs can be accommodated, please contact us via e-mail or at the fax or telephone numbers at the top of the page):

Rx-1 Single phase power only;
Rx-2 Dual phase power plus temperature & 2 DC channels (humidity optional);
Rx-3 Three phase power plus neutral (power only);
Rx-4 Three phase power plus neutral & temperature (humidity optional).


Home
Page

Top of
Page

Terms Defined

Model
Index